Load Break Switch and Combination Appliance
Your Professional Load Break Switch and Combination Appliance Supplier
Our goal is to become your true partner in the field of chassis truck for vcb in China. Shaanxi West Power Tongzhong Electrical Co., Ltd. is a leading manufacturer with over 20 years of experience, specializing in high quality vacuum circuit breakers, switchgears, and a wide range of electrical products. We have a skilled engineering team dedicated to refining every stage, from product development and process improvement to production oversight, ensuring every product delivered meets rigorous quality and performance standards. The price is competitive and the product is quality-assured, which is a good choice for your long-term cooperation.
-
(TZ15)-12/31.5 Indoor High Voltage Grounding Switch
1.Rated voltage:12kV. 2.Rated short-time withstand current:31.5kA. 3.Rated short-circuit duration:4s. 4.Rated short-circuit making current:80kA. 5.Rated peak withstand current:80kA. 6.Structure:Add to Inquiry -
VTZ-12GD-MT Vacuum Circuit Breaker Combination Electrical...
1.Rated Voltage:12kV. 2.Rated Frequency:50/60Hz. 3.Rated current :1250A. 4.Rated short-circuit breaking current:31.5kA. 5.Installation method: mining combined high-explosive cabinet. 6.ApplicableAdd to Inquiry -
FK(R)N12-24 Load Break Switch And Combination Appliance
1. Rated Voltage: 12kV. 2. Operating Mechanism: Combination of permanent magnet operation mechanism and spring operation mechanism.. 3. Installation Method: Mining explosion-proof switchgear.. 4.Add to Inquiry -
K18-7.2(F-C) Indoor Combination Appliance
1. Rated Voltage: 3.6kV to 7.2kV. 2. Installation Method: Floor handcart cabinet.. 3. Compatible Cabinet: Compatible with KYN18C-12 switchgear in a parallel F-C circuit structure.. 4. ProductAdd to Inquiry -
FK(R)N-12 Load Break Switch and Combination Appliance
1.Rated Voltage :12kV. 2.Rated Frequency:50/60Hz. 3. Rated breaking current:1200A. 4. Mechanical endurance :2000A. 5.Installation method: side-mounted fixed installation. 6.Applicable cabinet:Add to Inquiry -
VTZ(SC)-12GD Indoor Three-Position Vacuum Circuit Breaker
1. Rated Voltage: 12kV. 2. Installation Method: Fixed cabinet side installation.. 3. Compatible Cabinet: Compatible with HXGN-12 series ring main units.. 4. Product Compliance with Standards:Add to Inquiry -
FZ(R)N25-12 Load Break Switch and Combination Appliance
1. Rated Voltage: 10kV. 2. Installation Method: Side-mounted fixed installation.. 3. Compatible Cabinet: Compatible with HXGN-12 series ring main units.. 4. Product Compliance with Standards:Add to Inquiry
Why Choose Us
Our R&D: Our R&D team consists of senior technical experts with decades of experience in the design and manufacture of high and low voltage electrical equipment. Their expertise, combined with our advanced facilities, enables us to always lead industry trends and continuously optimize our product portfolio.
Quality control: We are able to accurately and efficiently produce a wide range of high-quality electrical products that comply with GB 1984-2024 and GB/T11022-2020 standards to ensure the highest quality.
Customization requirements: We know that our customers' needs are different, so each product can be designed according to the specific needs of the customer.
Our services: In the pre-sales stage, our team of experts will recommend the most suitable products according to the needs of customers and provide detailed technical consultation. During the sales period, we ensure timely delivery and provide installation guidance. For after-sales, we provide long-term technical support, warranty services and spare parts to help customers maximize the use of products and get reliable maintenance during use.
Advantages of Load Break Switch and Combination Appliance
Safe and reliable
It adopts a combination of permanent magnet mechanism + spring mechanism, and the permanent magnet mechanism is used for normal operation; when the permanent magnet mechanism fails, the manual closing and opening operations are safe and reliable. The circuit breaker and the cabinet can achieve reliable mechanical interlocking to ensure the safety of the operator.
High conductivity
Reasonable conductive circuit design meets the temperature rise level of 1.1 times the rated current;
Highly integrated and intelligent configuration
Wireless temperature intelligent monitoring solution can be added for self-power design, which is safe and maintenance-free. The combined electrical appliance is equipped with an electrically operated isolating switch and grounding switch, which does not require external equipment and supports one-button sequential control.

Specification of Load Break Switch and Combination Appliance
|
NO. |
Parameter name |
Unit |
Data |
|
1 |
Contact opening distance |
Mm |
9±1 |
|
2 |
Contact travel |
Mm |
3 ±0.5 |
|
3 |
Center distance between poles |
Mm |
150±1.5 |
|
4 |
Allowed wear thickness of moved and fixed contact |
Mm |
3 |
|
5 |
Average clsing speed |
M/s |
0.6±0.2 |
|
6 |
Average opening speed (average speed of first opening at 6mm) |
M/s |
1.1±0.2 |
|
7 |
Rated current pressure |
N |
2500±100/ 3100±200 |
|
8 |
Closing bounce |
Ms |
£2 |
|
9 |
Closing and opening are out of phase |
Ms |
£2 |
|
10 |
Closing time |
Ms |
30~70ms |
|
11 |
Opening time |
Ms |
20~50ms |
|
12 |
Isolation closing and opening action time |
S |
£40 |
|
13 |
Earthing closing and opening action time |
S |
£40 |
|
14 |
Main circuit resistance (after closing the circuit breaker and arc extinguishing chamber) |
Mw |
≤130 |
|
15 |
Energy storage power supply |
V |
DC110V(Voltage stabilization) |
|
16 |
Opening and closing circuits |
Passive shorting contacts |
|
Types of Load Break Switch and Combination Appliance
Air break switches: These switches use air as the arc extinguishing medium. They are typically used in outdoor substations and overhead distribution lines. Air break switches are simple in design and reliable in operation.
Oil break switches: Oil break switches utilize oil as the arc extinguishing medium. When the switch opens, the arc formed between contacts is submerged in oil, which helps in extinguishing it quickly. Oil break switches are often used in indoor substations and transformer installations.
Vacuum break switches: Vacuum break switches use a vacuum as the arc extinguishing medium. They offer fast and efficient interruption of currents, making them suitable for various applications including medium and high voltage systems.
Sf6 (sulfur hexafluoride) break switches: Sf6 break switches use sulfur hexafluoride gas as the arc extinguishing medium. They are often used in high voltage applications where rapid arc extinction and high dielectric strength are required. Sf6 break switches are commonly used in high voltage substations and transmission lines.
Solid dielectric load break switches: These switches use solid dielectric materials such as epoxy resin for insulation and arc extinction. They are compact, environmentally friendly, and require minimal maintenance. Solid dielectric load break switches are commonly used in medium voltage distribution systems.
Features of Load Break Switch and Combination Appliance
VTZ-12GD-MT vacuum circuit breaker combination electrical appliance is a special vacuum circuit breaker for underground mining with rated voltage of 12kV and AC 50/60Hz. It adopts permanent magnet mechanism and has mechanical manual closing and opening functions. It is suitable for various places with explosion-proof requirements for power facilities. The trolley unit is used in conjunction with PJG9-10 switch cabinet.
Distribution networks: Load break switches are commonly used in distribution networks to isolate sections of the grid for maintenance, repairs, or troubleshooting. They allow for the safe disconnection of power to specific areas without affecting the entire network.
Substations: Load break switches play a vital role in substations by providing isolation and sectionalization capabilities. They enable operators to isolate faulty equipment or sections of the substation while maintaining power flow to the rest of the system.
Overhead lines: Load break switches are often installed on overhead power lines to provide sectionalizing points and enable the isolation of specific line segments. They facilitate efficient fault location and restoration of power by isolating the affected section without disrupting service to other areas.
Transformer installations: Load break switches are used in transformer installations to isolate transformers from the rest of the electrical system for maintenance or replacement purposes.
Industrial facilities: Load break switches are employed in industrial facilities to provide isolation and control of electrical circuits feeding various equipment and machinery.
Commercial buildings
Load break switches are utilized in commercial buildings to isolate electrical circuits serving different areas or floors. They allow for localized maintenance or repairs without interrupting power supply to the entire building.
Emergency power systems
Load break switches are integrated into emergency power systems to provide manual or automatic transfer of power between utility and backup sources.
Railway electrification
Load break switches are used in railway electrification systems to isolate sections of the overhead catenary or third rail for maintenance or repair activities.
Packing and Shipping of Load Break Switch and Combination Appliance
|
Packing |
Box |
|
Shipping |
Shipped by road, sea, rail |