1. Rated Voltage: 12kV
2. Operating Mechanism: Modular Operating Mechanism.
3. Installation Method: Handcart with a central operating mechanism.
4. Applicable cabinet: ISM switch cabinet type used at home and abroad.
5. Product Compliance with Standards: GB/T11022-2011.
6. Product Advantages: E2-C2-M2 performance, easy maintenance, high conductivity, and perfect replacement.
Send Inquiry
Product Introduction

 

This renovation adopts the basic model of our company's VTZ-12 Vacuum Circuit Breaker, with a design change and a modular operating mechanism, which perfectly matches the corresponding ISM products and is suitable for various industrial and mining enterprises and power grid equipment. The trolley unit is used in conjunction with the KYN28A-12 switch cabinet, and can also be used as a fixed unit with corresponding mechanical interlocking for fixed cabinets such as XGN2. The VTZ series mechanism can also be used for the renovation of many other old switches of international brands; this case is used for the replacement and renovation of Trede ISM circuit breakers.

 

 
Product Specifications

 

Specification Sheet

No.

Name

Unit

Data

1

Rated Voltage

kV

12

2

Rated Frequency

Hz

50/60

3

Rated Current

A

630/1250/1600

4

Rated Power Frequency Withstand Voltage

kV

48(Common value) /42(Across the isolating

Distance)

5

Rated Lightning Impulse Withstand Voltage

kV

85(Common value) /75(Across the isolating Distance)

6

Rated Short-Circuit Breaking Current

kA

25/31.5

7

Rated Short-Circuit Making Current (Peak)

kA

63/80

8

Rated Withstand Current (Peak)

kA

63/80

9

Rated Duration of Short-Circuit

s

4

10

Operating Cycles at Rated Short-Circuit Breaking Current

Cycles

E2

11

Mechanical Endurance

Times

10000

12

Standard Operating Sequence

-

O-0.3s-CO-180s-CO

13

Allowable Wear Thickness of Contact

mm

≤3

Mechanical Characteristics

No.

Name

Unit

Data

1

Clearance between Moved and Fixed Contact

mm

9±1

2

Contact Overtravel

mm

3.5±0.5

3

Average Closing Speed

m/s

0.7±0.2

4

Average Opening Speed (Average Speed of First Opening at 6mm)

m/s

1.1±0.2

5

Rated Contact Pressure

N

                 2500±200N(25kA)

                 3100±200N(31.5kA)

6

Closing Time

ms

3070

7

Opening Time

ms

2050

8

Contact Bouncing Duration at Closing Operation

ms

≤2

9

No-Simultaneity of Closing/Opening Operations of 3-Phase

ms

≤2

Product Advantages

TAVRIDA ISM Indoor Vacuum Circuit Breaker Retrofit has many advantages:

  • Circuit Breaker Performance

    E2-C2-M2

  • Easy Maintenance

    Simple and convenient maintenance: With the modular structure, the closing and opening coils can be replaced without removing other components. Users can easily replace them, and no testing or adjustment is required after replacement, making subsequent operation and maintenance more convenient.

  • High Conductivity

    Reasonable conductive circuit design meets the temperature rise level of 1.1 times the rated current.

  • Perfect Replacement

    This transformation solution can perfectly replace ISM products, making it easy to maintain and replace, solving urgent problems for electricity users.

Product Applications 

TAVRIDA ISM Indoor Vacuum Circuit Breaker Retrofit has many applications:

Power plants

Industrial fields

Power grid systems

Power infrastructures

 

Product Outline Drawing 

 

01

 

 

Secondary Wiring Diagram

 

02

Hot Tags: tavrida ism indoor vacuum circuit breaker retrofit, China tavrida ism indoor vacuum circuit breaker retrofit manufacturers, suppliers, factory, technical support, Alternative Design Of ABB Circuit Breaker, Retrofit Of Siemens Circuit Breaker