Products
TAVRIDA ISM Indoor Vacuum Circuit Breaker Retrofit
2. Operating Mechanism: Modular Operating Mechanism.
3. Installation Method: Handcart with a central operating mechanism.
4. Applicable cabinet: ISM switch cabinet type used at home and abroad.
5. Product Compliance with Standards: GB/T11022-2011.
6. Product Advantages: E2-C2-M2 performance, easy maintenance, high conductivity, and perfect replacement.
This renovation adopts the basic model of our company's VTZ-12 Vacuum Circuit Breaker, with a design change and a modular operating mechanism, which perfectly matches the corresponding ISM products and is suitable for various industrial and mining enterprises and power grid equipment. The trolley unit is used in conjunction with the KYN28A-12 switch cabinet, and can also be used as a fixed unit with corresponding mechanical interlocking for fixed cabinets such as XGN2. The VTZ series mechanism can also be used for the renovation of many other old switches of international brands; this case is used for the replacement and renovation of Trede ISM circuit breakers.
Product Specifications
Specification Sheet
|
No. |
Name |
Unit |
Data |
|
1 |
Rated Voltage |
kV |
12 |
|
2 |
Rated Frequency |
Hz |
50/60 |
|
3 |
Rated Current |
A |
630/1250/1600 |
|
4 |
Rated Power Frequency Withstand Voltage |
kV |
48(Common value) /42(Across the isolating Distance) |
|
5 |
Rated Lightning Impulse Withstand Voltage |
kV |
85(Common value) /75(Across the isolating Distance) |
|
6 |
Rated Short-Circuit Breaking Current |
kA |
25/31.5 |
|
7 |
Rated Short-Circuit Making Current (Peak) |
kA |
63/80 |
|
8 |
Rated Withstand Current (Peak) |
kA |
63/80 |
|
9 |
Rated Duration of Short-Circuit |
s |
4 |
|
10 |
Operating Cycles at Rated Short-Circuit Breaking Current |
Cycles |
E2 |
|
11 |
Mechanical Endurance |
Times |
10000 |
|
12 |
Standard Operating Sequence |
- |
O-0.3s-CO-180s-CO |
|
13 |
Allowable Wear Thickness of Contact |
mm |
≤3 |
Mechanical Characteristics
|
No. |
Name |
Unit |
Data |
|
1 |
Clearance between Moved and Fixed Contact |
mm |
9±1 |
|
2 |
Contact Overtravel |
mm |
3.5±0.5 |
|
3 |
Average Closing Speed |
m/s |
0.7±0.2 |
|
4 |
Average Opening Speed (Average Speed of First Opening at 6mm) |
m/s |
1.1±0.2 |
|
5 |
Rated Contact Pressure |
N |
2500±200N(25kA) 3100±200N(31.5kA) |
|
6 |
Closing Time |
ms |
30~70 |
|
7 |
Opening Time |
ms |
20~50 |
|
8 |
Contact Bouncing Duration at Closing Operation |
ms |
≤2 |
|
9 |
No-Simultaneity of Closing/Opening Operations of 3-Phase |
ms |
≤2 |
Product Advantages
TAVRIDA ISM Indoor Vacuum Circuit Breaker Retrofit has many advantages:
-
Circuit Breaker Performance
E2-C2-M2
-
Easy Maintenance
Simple and convenient maintenance: With the modular structure, the closing and opening coils can be replaced without removing other components. Users can easily replace them, and no testing or adjustment is required after replacement, making subsequent operation and maintenance more convenient.
-
High Conductivity
Reasonable conductive circuit design meets the temperature rise level of 1.1 times the rated current.
-
Perfect Replacement
This transformation solution can perfectly replace ISM products, making it easy to maintain and replace, solving urgent problems for electricity users.
Product Applications
TAVRIDA ISM Indoor Vacuum Circuit Breaker Retrofit has many applications:
Power plants
Industrial fields
Power grid systems
Power infrastructures
Product Outline Drawing

Secondary Wiring Diagram

Hot Tags: tavrida ism indoor vacuum circuit breaker retrofit, China tavrida ism indoor vacuum circuit breaker retrofit manufacturers, suppliers, factory, technical support, Alternative Design Of ABB Circuit Breaker, Retrofit Of Siemens Circuit Breaker
-
3AE Siemens Circuit Breaker Retrofitview more> -
VTZ/CS-12 Vacuum Circuit Breaker with Lateral Operating M...view more> -
KYN61-40.5 Indoor Armored Metal-Enclosed Switch Equipmentview more> -
12kV Sensorview more> -
Alternative Design Of ABB Circuit Breakerview more> -
Retrofit Of Siemens Circuit Breakerview more>