Products

3AE Siemens Circuit Breaker Retrofit
2. Operating Mechanism: Modular Operating Mechanism.
3. Installation Method: Handcart with a central operating mechanism.
4. Compatible Cabinet: 3AE5 domestic and international switchgear models using NXAIR advancing mechanism.
5. Product Compliance with Standards: GB/T11022-2011.
6. Product Advantages: E2-C2-M2 performance, easy maintenance, high conductivity, and perfect replacement.
The VTZ series operating mechanism can be used for the retrofit and upgrading of aging vacuum circuit breakers from various international brands. This particular project involves the retrofit of a Siemens 3AE5 vacuum circuit breaker by installing an NXAIR-compatible advancing mechanism, helping improve equipment reliability while making effective use of the existing switchgear structure.
The 3AE Siemens Circuit Breaker Retrofit Solution is designed for indoor switchgear with a rated voltage of 17.5kV and an operating frequency of 50/60Hz. It adopts a modular operating mechanism and is suitable for various industrial enterprises, power distribution systems, and power grid equipment.
The circuit breaker can be configured as a withdrawable truck-mounted unit for use with KYN28A-12 switchgear, or as a fixed unit equipped with the corresponding mechanical interlocking components for fixed-type cabinets such as XGN2. Through customized structural adaptation and modular design, the retrofit solution provides reliable switching performance while reducing the need for extensive modifications to existing equipment.
This solution is suitable for aging equipment replacement, switchgear renovation, and circuit breaker upgrading projects, helping customers extend the service life of existing switchgear, improve operational reliability, and reduce the overall cost and complexity of equipment replacement.
Product Specifications
Specification Sheet
|
No. |
Name |
Unit |
Data |
|
1 |
Rated Voltage |
kV |
12 |
|
2 |
Rated Frequency |
Hz |
50/60 |
|
3 |
Rated Current |
A |
630/1250/1600/2000/2500 |
|
4 |
Rated Power Frequency Withstand Voltage |
kV |
28(Across the Contact Gaps) / 28(To Ground) |
|
5 |
Rated Lightning Impulse Withstand Voltage |
kV |
95 |
|
6 |
Rated Short-Circuit Breaking Current |
kA |
25/31.5/40 |
|
7 |
Rated Short-Circuit Making Current (Peak) |
kA |
63/80/100 |
|
8 |
Rated Withstand Current (Peak) |
kA |
63/80/100 |
|
9 |
Rated Duration of Short-Circuit |
s |
4 |
|
10 |
Operating Cycles at Rated Short-Circuit Breaking Current |
Cycles |
E2 |
|
11 |
Mechanical Endurance |
Times |
10000 |
|
12 |
Standard Operating Sequence |
- |
O-0.3s-CO-180s-CO |
|
13 |
Allowable Wear Thickness of Contact |
mm |
≤3 |
Mechanical Characteristics
|
No. |
Name |
Unit |
Data |
|
1 |
Clearance between Moved and Fixed Contact |
mm |
9±1 |
|
2 |
Contact Overtravel |
mm |
3.5±0.5 |
|
3 |
Average Closing Speed |
m/s |
0.7±0.2 |
|
4 |
Average Opening Speed (Average Speed of First Opening at 6mm) |
m/s |
1.1±0.2 |
|
5 |
Rated Contact Pressure |
N |
2500±200N(25kA) 3100±200N(31.5kA) 4800±300N(40kA) |
|
6 |
Closing Time |
ms |
30~70 |
|
7 |
Opening Time |
ms |
20~50 |
|
8 |
Contact Bouncing Duration at Closing Operation |
ms |
≤2 |
|
9 |
No-Simultaneity of Closing/Opening Operations of 3-Phase |
ms |
≤2 |
Product Advantages
3AE Siemens Circuit Breaker Retrofit has many advantages:
-
Circuit Breaker Performance
Meets E2-C2-M2 performance requirements, ensuring reliable electrical and mechanical endurance as well as stable switching performance under demanding operating conditions. This makes the circuit breaker suitable for applications requiring frequent operation and reliable fault interruption.
-
Easy Maintenance
The modular mechanism design allows for the replacement of closing and opening coils without the need to dismantle other components. Users can easily replace the coils, and no testing or adjustment is required after replacement, making future operation and maintenance more convenient.
-
High Conductivity
The rationally designed conductive circuit meets the temperature rise requirements at 1.1 times the rated current, ensuring reliable current-carrying capacity and stable electrical performance. This design also helps reduce heat accumulation during continuous operation and enhances the overall reliability of the circuit breaker.
-
Perfect Replacement
This retrofit solution perfectly replaces aging Siemens products, making maintenance and replacement easier, addressing the urgent needs of electricity customers.
Product Applications
3AE Siemens Circuit Breaker Retrofit has many applications:
Power plants
Industrial fields
Power grid systems
Power infrastructures
Product Outline Drawing

Secondary Wiring Diagram

Hot Tags: 3ae siemens circuit breaker retrofit, China 3ae siemens circuit breaker retrofit manufacturers, suppliers, factory, Alternative Design Of ABB Circuit Breaker, technical support, Retrofit Of Siemens Circuit Breaker
-
24kV Epoxy Contact Box for KYN28A-24 Switchgear Insulationview more> -
Chassis Truck for KYN61-40.5 Switchgearview more> -
Alternative Design Of ABB Circuit Breakerview more> -
Retrofit Of Siemens Circuit Breaker from XDTZview more> -
JN15-12 Indoor Grounding Switchview more> -
VTZ-12(K59)Indoor High Voltage Vacuum Circuit Breakerview more>