VTZ/CS-12 vacuum circuit breaker with lateral operating mechanism is an indoor switchgear for rated voltage 12kV and AC frequency 50/60Hz. Featuring a narrow modular design, it is suitable for industrial and mining enterprises, power plants, medium and small generators for power transmission, and secondary substations within the power system for power reception and transmission, as well as the startup of large high-voltage motors.
Product Specifications
Specification Sheet
|
No. |
Name |
Unit |
Data |
|
1 |
Rated Voltage |
kV |
12 |
|
2 |
Rated Frequency |
Hz |
50/60 |
|
3 |
Rated Current |
A |
630/1250 |
|
4 |
Rated Power Frequency Withstand Voltage |
kV |
48(Across the Contact Gaps) / 42(To Ground) |
|
5 |
Rated Lighting Impulse Withstand Voltage |
kV |
75 |
|
6 |
Rated Short-Circuit Breaking Current |
kA |
25/31.5 |
|
7 |
Rated Short-Circuit Making Current (Peak) |
kA |
63/80 |
|
8 |
Rated Withstand Current (Peak) |
kA |
63/80 |
|
9 |
Rated Duration of Short-Circuit |
s |
4 |
|
10 |
Operating Cycles at Rated Short-Circuit Breaking Current |
Cyles |
E2 |
|
11 |
Mechanical Endurance |
Times |
10000 |
|
12 |
Standard Operating Sequence |
- |
O-0.3s-CO-180s-CO O-180s-CO-180s-CO |
|
13 |
Allowable Wear Thickness of Contact |
mm |
≤3 |
Mechanical Characteristics
|
No. |
Name |
Unit |
Data |
|
1 |
Clearance between Moved and Fixed Contact |
mm |
9±1 |
|
2 |
Contact Overtravel |
mm |
3.5±0.5 |
|
3 |
Average Closing Speed |
m/s |
0.7±0.2 |
|
4 |
Average Opening Speed (Average Speed of First Opening at 6mm) |
m/s |
1.1±0.2 |
|
5 |
Rated Contact Pressure |
N |
2500±200N(25kA) 3100±200N(31.5kA) |
|
6 |
Closing Time |
ms |
35~70 |
|
7 |
Opening Time |
ms |
20~50 |
|
8 |
Contact Bouncing Duration at Closing Operation |
ms |
≤3 |
|
9 |
No-Simultaneity of Closing/Opening Operations of 3-Phase |
ms |
≤2 |
Product Advantages
VTZ/CS-12 vacuum circuit breaker with lateral operating mechanism has many advantages:
Breaker performance:
E2-C2-M2
01
Stability and reliability:
1). Achieves visualization of the main conductive plug connection state and process in withdrawable type switchgear.
2). Achieves visibly apparent primary air isolation breaks in withdrawable type switchgear.
3). The smallest volume among similar products.
02
Excellent insulation performance:
The main conductive circuit adopts APG high-strength epoxy resin composite insulated cylinder, which exceeds the IEC standard in terms of insulation performance.
03
High adaptability:
The three phases of the circuit breaker are arranged from inside to outside, with the minimum cabinet depth of 550mm, making it suitable for various environments. The circuit breaker can be equipped with a mechanical interlock for easy interlocking with the isolating switch and grounding switch of cabinet, ensuring high safety.
04
Product Applications
VTZ/CS-12 vacuum circuit breaker with lateral operating mechanism has many applications:
Product Outline Drawing

Secondary Wiring Diagram

Hot Tags: vtz/cs-12 vacuum circuit breaker with lateral operating mechanism, China vtz/cs-12 vacuum circuit breaker with lateral operating mechanism manufacturers, suppliers, factory, indoor mv vacuum circuit breaker, VS1 12 Vacuum Circuit Breaker with Lateral Operating Mechanism, ZN85 40 5 Vacuum Circuit Breaker, VTZ CS 12 Vacuum Circuit Breaker with Lateral Operating Mechanism, ZN39 40 5 Vacuum Circuit Breaker, VTZ 12C Vacuum Circuit Breaker with Lateral Operating Mechanism