Products
24kV Vacuum Interrupter for Vacuum Circuit Breaker
2. Installation Method: Can be mounted inside an insulated cylinder or embedded epoxy resin.
3. Suitable Carrier: Suitable for 24kV circuit breakers, KYN28A-24 type cabinets, etc.
4. Product Advantages: Strong arc extinguishing capability, high insulation level, long life, compact and lightweight, easy maintenance, no explosion risk, pollution-free, and low noise.
Every time a vacuum circuit breaker interrupts a fault current, the real work happens inside one component: the vacuum interrupter. It's the heart of the breaker - a sealed ceramic tube containing the fixed and moving contacts, housed in a high-vacuum environment (typically better than 10⁻⁴ Pa). When the contacts separate under fault conditions, the arc that forms is contained within the vacuum envelope. Because vacuum has such high dielectric strength, the arc is extinguished within the first current zero - typically in less than half a cycle. Our 24kV vacuum interrupter is rated for 24kV with a lightning impulse withstand of 125kV and short-circuit breaking capacity up to 31.5kA. It delivers the interruption performance that 24kV switchgear - whether in mining, railway traction, or industrial distribution - depends on to protect equipment and personnel.
Product Specifications
Specification Sheet
|
No. |
Name |
Unit |
Data |
Voltage Parameters
|
1 |
Rated Frequency (fr) |
Hz |
50/60 |
|
2 |
Rated Voltage (Ur) |
kV |
24 |
|
3 |
Rated Short-Time(1 min) Power Frequency Withstand Voltage (Ud) |
kV |
65 |
|
4 |
Rated Lightning Impulse Withstand Voltage (Peak) (Up) |
kV |
125 |
Current Parameters
|
1 |
Rated Current (Ir) |
A |
630/1250/1600/2000/2500 |
|
2 |
Rated Short-Circuit Breaking Current (Isc) |
kA |
25/31.5 |
|
3 |
Operating Cycles at Rated Short-Circuit Breaking Current |
Cycles |
30 |
|
4 |
Rated Short-Time Withstand Current (Ik) |
kA |
25/31.5 |
|
5 |
Rated Duration of Short-Circuit (tk) |
s |
4 |
|
6 |
Rated Withstand Current (Peak) (Ip) |
kA |
63/80 |
|
7 |
Rated Short-Circuit Making Current (IMC) |
kA |
63/80 |
|
8 |
Rated Short-Circuit Breaking Current DC Component |
% |
40 |
|
9 |
Standard Operating Sequence |
mm |
O-0.3s-CO-180s-CO O-180s-CO-180s-CO (≥40kA) |
Mechanical Parameters
|
1 |
Mass of Moving Parts |
kg |
1.1~2.5 |
|
2 |
Self-Closing Force of Contact |
N |
100±40~230±100 |
|
3 |
Rated Contact Pressure |
N |
2500±200~3200±100 |
Requirements for Switch Mechanical Characteristics
|
1 |
Clearance between Moved and Fixed Contact |
mm |
15±1 |
|
2 |
Average Opening Speed (from 75% of the contact gap to contact closed position) |
m/s |
1.5±0.2 |
|
3 |
Average Closing Speed (from 30% of the contact gap to contact closed position) |
m/s |
0.8±0.2 |
|
4 |
Contact Closing Bounce Time |
ms |
≤2 |
|
5 |
No-Simultaneity of Contact Closing and Opening |
ms |
≤2 |
|
6 |
Contact Opening Rebound Amplitude |
mm |
≤2 |
Lifespan
|
1 |
Storage Period |
Years |
20 |
|
2 |
Mechanical Endurance |
Times |
10000 |
|
3 |
Allowable Wear Thickness of Contact |
mm |
3 |
Product Advantages
In a vacuum environment, the arc is easily extinguished, enabling fast and effective circuit interruption with a high breaking capacity.
Vacuum offers excellent insulating properties, capable of withstanding high voltages, ensuring the safe operation of the circuit.
The internal structure is simple, free from oxidation problems that could affect the contacts, resulting in long mechanical and electrical life.
Supports the design of smaller, more compact equipment.
Basically no special maintenance is required, and the operation reliability is high.
During operation, there is no danger of explosion and no harmful gases or substances are emitted, making it environmentally friendly.
Produces minimal noise during operation.
Product Applications
24kV vacuum interrupter for vacuum circuit breaker is widely used in 24kV distribution systems across various industries such as metallurgy, mining, petroleum, chemical engineering, railways, broadcasting, communications, and industrial high-frequency heating.
Product Outline Drawing

630A-1600A

2000A-3150A (Used for embedded pole)
Hot Tags: 24kV Vacuum Interrupter for Vacuum Circuit Breaker, China 24kV Vacuum Interrupter for Vacuum Circuit Breaker manufacturers, suppliers, factory, 40 5kV Vacuum Interrupter for Vacuum Circuit Breaker, CT 58 Control Cable Assembly, 12kV Insulating Pulling Pole Assembly, 24kV Vacuum Interrupter for Vacuum Circuit Breaker, 12kV Vacuum Interrupter for Vacuum Circuit Breaker, other accessories for vcb
-
CT-58 Aviation Connector Secondary Harness for VCBview more> -
40.5kV Vacuum Interrupter for Vacuum Circuit Breakerview more> -
12kV Vacuum Interrupter for Vacuum Circuit Breakerview more> -
CT-58 Control Cable Assemblyview more> -
12kV Sensorview more> -
12kV Insulating Pulling Pole Assembly For Vacuum Circuit ...view more>