Globally accepted voltage level classifications in industry standards
Low voltage: AC ≤ 1000V, DC ≤ 1500V
Medium voltage: AC 1kV ~ 35kV
High voltage: AC 35kV ~ 220kV
Ultra-high voltage: 330kV and above.
Today Let's Talk About High-Voltage Switchgear-AC 35kV ~ 220kV

How Many Types of High-Voltage Switchgear Are There?
1. AIS - Air-insulated open-type switchgear.
Air-insulated open-type switchgear is the most traditional and classic form of high-voltage substation.
Core equipment of AIS:
-Circuit breaker: The core for breaking and making current. Typically a pillar-type or tank-type SF6 circuit breaker.
-Disconnecting switch: Provides visible electrical isolation points for safe maintenance.
-Current transformer: Used for measurement and protection. Mostly oil-immersed or SF6 gas-insulated independent porcelain pillar devices.
-Voltage transformer: Typically uses a capacitive voltage transformer, also an independent tank or pillar-type device.
-Surge Arrester: Metal oxide surge arrester, protects equipment from overvoltage damage.
-Grounding Switch: Manual or electric, used to reliably ground lines or busbars.
Features of AIS : Relatively low investment. However, requires frequent power outages for cleaning and maintenance.
Application of AIS:
Suitable for suburban and remote substations, and areas where land costs are not a major concern.
2. GIS - Gas-Insulated Metal-Enclosed Switchgear
Gas-insulated metal-enclosed switchgear is the mainstream and high-end choice for modern high-voltage substations.
Core Equipment of GIS:
-Circuit Breaker: Core component, mostly compressed air or self-energized SF₆ circuit breakers.
-Disconnecting Switch & Grounding Switch: Typically three-position switches, compact in structure and with low operating torque.
-Current Transformer: Usually uses Rokowski coils, directly mounted on the conductor, small in size, high in accuracy, and without magnetic saturation.
-Voltage Transformer: Capacitive voltage divider type or electromagnetic type, integrated in a gas chamber.
-Surge arrester: Metal oxide surge arrester, sealed in a separate gas chamber filled with slightly lower pressure SF₆ or nitrogen.
-Busbar: The main conductor is supported on a basin-type insulator and enclosed within a busbar drum.
Features of GIS:
Involves SF₆ gas pollution. It has a very small footprint, long maintenance cycles, and complex maintenance. Although operating costs are low, the initial investment is very high.
Applications of GIS:
Suitable for: city centers, underground, mountainous areas, islands, and industrial plants.
Products Description
GW4-126 Outdoor High Voltage Isolating Switch is a 3-phase AC high-voltage electrical appliance, used in power systems with a voltage of 40.5, for no-load switching in high-voltage lines, and for electrical isolation between high-voltage busbars, circuit breakers and other electrical equipment under maintenance and energized high-voltage lines.