What caused the breakage failure?
During the opening operation of a vacuum circuit breaker, a metal vapor arc forms between the contacts. If the Arc is not controlled, it will contract into a slender column, with the cathode spots concentrated in a very small area on the contact surfaces. As a result, energy becomes highly concentrated, causing a sharp rise in local temperature, and deep pits will quickly form on the contacts-which may even lead to circuit breaker failure. This type of "concentrated ablation" is precisely the scenario that vacuum arc chambers must avoid at all cost.
Cause Decomposition
The idea behind an axial magnetic field is to apply a magnetic field parallel to the arc axis. When charged particles move in a magnetic field, they experience the Lorentz force. Electrons and ions no longer travel in straight lines from cathode to anode; instead, they spiral around the magnetic field lines. Macroscopically, the arc is no longer a stationary thin column. It is driven to rotate rapidly or spread out over the contact surface, and the cathode spots are correspondingly distributed over a larger area. The energy is "spread out," the heat load per unit area drops significantly, and contact erosion is naturally reduced.
How to generate a vertical magnetic field
A common way to produce an axial magnetic field is to use cup-shaped contacts or spiral-slotted contacts. When current flows through the contacts, it generates an axial magnetic field by itself, without the need for an external coil. This design makes the arc rotate automatically when interrupting large currents, reducing contact wear while improving interrupting capability.
Has become a mainstream technical solution
It should be noted that a stronger axial magnetic field is not always better. If the field is too weak, the arc remains concentrated; if it is too strong, the arc voltage rises and energy injection actually increases. In engineering, the contact structure must be optimized according to the rated current and interrupting capacity. At present, axial magnetic field contacts have become one of the mainstream technical solutions for medium- and high-voltage vacuum interrupters, and their effectiveness has been verified by extensive interruption tests.
Simply put, the axial magnetic field makes the arc "run around while burning" rather than "squat in one spot and burn."

12KV/24KV/40.5KV vacuum circuit breakers
Reliable Vacuum Circuit Breakers, Customized for Global Clients
Professional Technical&Sales Team | On-Time Delivery
Shaanxi West Power Tongzhong Electrical Co., Ltd.
Our address
No.1 East Gaoxin Avenue, High-tech Development Zone, Baoji City, Shaanxi Province, China
Phone Number
+86 18091766017(WhatsApp/Wechat)