Products

Indoor Vacuum Contactor Combination Electrical Appliance Retrofit Solution
2.Rated Frequency:50/60Hz
3.Rated current:630A
4.Rated short-circuit breaking current:31.5kA
5.Installation method: center-mounted trolley
6.Applicable cabinet: switch cabinet type suitable for VCM combination electrical appliances
7.Product compliance standard: GB/T11022-2011
8.Product advantages:Simple and convenient maintenance,high conductivity: Perfect replacement
Indoor Vacuum Contactor Combination Electrical Appliance Retrofit Solution
The Indoor Vacuum Contactor Combination Electrical Appliance Retrofit Solution is based on our company's VTZ-12 indoor high-voltage vacuum circuit breaker platform. Through optimized structural design, component modifications, and a modular operating mechanism, the retrofit solution is designed to achieve a precise and reliable match with the corresponding VCM vacuum contactor combination electrical appliances. It provides an effective solution for switchgear upgrading and renovation projects, helping customers improve equipment performance while making full use of their existing switchgear infrastructure.
This retrofit case was developed for the replacement and renovation of Mingji Electric's VCM vacuum contactor combination electrical appliances. By adopting a customized configuration and modular design, the existing equipment can be upgraded with minimal structural changes, helping simplify installation and reduce the overall cost and time associated with equipment replacement.
We also provide high-quality alternatives to ABB, Schneider, and Siemens vacuum circuit breakers. Our alternative products are designed to provide comparable performance, reliable operation, and compatibility with relevant applications, while offering a more competitive and cost-effective solution. This allows customers to upgrade or replace existing equipment while achieving an excellent balance between performance, reliability, and overall value for money.
Commitment to Excellence
At Shaanxi West Power Tongzhong Electrical Co., Ltd., our commitment to excellence is reflected in every aspect of our business. From product research and development to manufacturing, quality control, and customer service, we continuously strive to deliver high-quality products and professional solutions that meet the evolving needs of the electrical industry.
We continuously improve our management systems and production processes, attract and develop experienced technical and professional talent, and make full use of high-quality social and industrial resources. By integrating these strengths, we are building a robust and efficient industrial chain covering the R&D, production, testing, and supply of high-quality electrical products.
With a strong focus on technological innovation, product reliability, and continuous improvement, we aim to enhance our manufacturing capabilities and provide customers with stable, efficient, and dependable electrical solutions. Through close cooperation with suppliers, technical partners, and customers, we continue to optimize our resources and capabilities, creating a solid foundation for long-term development and sustainable growth.
Product Specifications
Specification Sheet
|
No. |
Name |
Unit |
Data |
|
1 |
Rated Voltage |
kV |
12 |
|
2 |
Rated Frequency |
Hz |
50/60 |
|
3 |
Rated current |
A |
630 |
|
4 |
Rated power-frequency withstand voltage |
kV |
48(Across the contact gaps ) /42(To ground) |
|
5 |
Rated lightning impulse withstand voltage |
kV |
75 |
|
6 |
Rated short-circuit breaking current |
kA |
31.5 |
|
7 |
Rated-short-circuit making current (peak) |
kA |
80 |
|
8 |
Rated withstand current (peak) |
kA |
80 |
|
9 |
Rated duration of short circuit |
s |
4 |
|
10 |
Operating cycles at rated short-circuit breaking current |
Times |
E2 |
|
11 |
Mechanical endurance |
Times |
10000 |
|
12 |
Standard Operating sequence |
- |
O-0.3s-CO-180s-CO |
|
13 |
All0wable wearing thickness of contacts |
mm |
≤3 |
Mechanical Characteristics
|
No. |
Name |
Unit |
Data |
|
1 |
Clearance between open contacts |
mm |
9±1 |
|
2 |
Over-travel |
mm |
3.5±0.5 |
|
3 |
Average closing speed |
m/s |
0.7±0.2 |
|
4 |
Average opening speed(average speed at 6mm of initial opening) |
m/s |
1.1±0.2 |
|
5 |
Rated added external contact final force |
N |
3100±200N(31.5kA) |
|
6 |
Make time |
ms |
30~70 |
|
7 |
Breaking time |
ms |
20~50 |
|
8 |
Contact bouncing duration at closing operation |
ms |
≤2 |
|
9 |
Closing/opening no-simultaneity of 3-phase contacts |
ms |
≤2 |
Product Advantages
Retrofit of indoor vacuum contactor combination electrical appliances has many advantages:
-
Circuit Breaker Performance
E2-C2-M2
This makes it suitable for applications requiring frequent switching, reliable fault interruption, and long-term.
-
Simple and convenient maintenance
With modular structure, the replacement of closing and opening coils does not require the removal of other components. Users can easily replace them, and no testing and adjustment are required after replacement, making later operation and maintenance more convenient.
-
High Conductivity
Reasonable design of the conductive circuit ensures that the temperature rise remains within the specified limits at 1.1 times the rated current, providing reliable current-carrying performance. This helps improve the stability and safety of the circuit breaker during continuous operation.
-
Perfect replacement
This transformation plan can perfectly replace VCM combination electrical appliances, which is easy to maintain and replace, and provides customers with fast and convenient power grid upgrade services.
Product Applications
Retrofit of indoor vacuum contactor combination electrical appliances has many applications:

Power plants
Industrial fields
Power grid systems
Power infrastructures
Product Outline Drawing

Secondary Wiring Diagram

Hot Tags: Indoor Vacuum Contactor Combination Electrical Appliance Retrofit Solution, China Indoor Vacuum Contactor Combination Electrical Appliance Retrofit Solution manufacturers, suppliers, factory, Retrofit Of Siemens Circuit Breaker, technical support, Alternative Design Of ABB Circuit Breaker
-
Alternative Design Of Siemens Inida 3AE Retrofit Exampleview more> -
ABB Fixed Type Vacuum Circuit Breaker Alternative Replace...view more> -
Eaton Model W-VACX Vacuum Circuit Breaker Retrofitview more> -
TAVRIDA ISM Indoor Vacuum Circuit Breaker Retrofitview more> -
3AE Siemens Circuit Breaker Retrofitview more> -
Alternative Design Of ABB Circuit Breakerview more>