What is the Insulation Resistance Test for Vacuum Circuit Breakers?

The insulation resistance test for vacuum circuit breakers is a key test for evaluating their insulation performance. The following is a detailed explanation:

1.Test Locations

Main circuit to ground: Insulation resistance between conductive parts (such as contacts and conductive rods) and the grounded housing.

Between phases (multi-pole circuit breakers): Insulation resistance between the conductive parts of each phase.

2. Test Instruments

Megohmmeter (Insulation Resistance Tester):

Voltage: Typically 1000V or 2500V DC (2500V is commonly used for 12kV circuit breakers).

Range: 0-10GΩ or higher (high resistance values require interference prevention).

Notes:

Before testing, disconnect the power supply and discharge the insulation (including parasitic capacitance).

Ambient humidity should be ≤ 80% to prevent condensation on the surface from affecting the results.

3. Test Procedure

1) Wiring:

Ground test: Connect the "L" terminal of the megohmmeter to the main circuit and the "E" terminal to the grounded housing.

Interruption test: In the open state, connect "L" to the moving contact and "E" to the static contact.

2) Measurement:

Read the stable value after 60 seconds at a constant speed (for manual megohmmeter) or in automatic mode (for absorption ratio test, record the 15s/60s ratio). 4) Recovery:

Discharge again after the test to prevent residual voltage hazards.

4. Acceptance Criteria

Test Location

Minimum Requirements (Normal Temperature

Remarks

Main Circuit to Ground

≥1000MΩ

12kV and Above Equipment

Inter-contact Gap

≥5000MΩ

Vacuum interrupter key indicators

Between Phases (Open)

≥1000MΩ

 1000MΩ Multi-Pole Circuit Breakers

 

Abnormal Detection:

Value 50% below the standard: Moisture or contamination may be present.

Value drops sharply or approaches zero: Insulation breakdown or severe defects.

Example (12 kV vacuum circuit breaker)

Test voltage: 2500 V DC

Normal values:

Between interrupters: 10 GΩ (new interrupter chambers can reach over 100 GΩ)

To ground: 5 GΩ

Fault case: If the interrupter resistance is only 100 MΩ, the vacuum level may have deteriorated and the interrupter chamber may need to be replaced.

Insulation resistance testing is a fundamental maintenance measure for vacuum circuit breakers and should be combined with other tests (such as loop resistance and withstand voltage testing) to comprehensively assess the equipment's condition.

vtz-12kf-fast-vacuum-circuit-breaker

VTZ-12KF Fast Vacuum Circuit Breaker by Shaanxi West Power Tongzhong Electrical Co., Ltd. Is an indoor switchgear for rated voltage 12kV, AC 50/60Hz. It adopts modular operating mechanism and is suitable for various industrial and mining enterprises and power grid equipment. The trolley unit is used in conjunction with the KYN28A-12 switch cabinet. It can also be used as a fixed unit and equipped with corresponding mechanical interlocking for XGN2 and other fixed cabinets.

VTZ-12KF Fast Vacuum Circuit Breaker has many advantages:

1.Performance of circuit breaker:

E2-C2-M2

2.High adaptability:

This product is completely consistent with the cabinet switch size of the conventional KYN28-12 series, and does not require special cabinet design, which is suitable for a variety of occasions for transforming the power environment.

3.High conductivity:

Reasonable conductive circuit design, meeting the temperature rise level of 1.1 times the rated current;

4.Simple and reliable structure:

permanent magnet mechanism, three-phase independent design;

 

For more details ,pls cotact us :

logo2Shaanxi West Power Tongzhong Electrical Co., Ltd.

Contact: Ms.Grace Liu (Director of Sales Department)

Tel: +86 917 3661109 Fax: +86 917 6739416

Email:xdtz04@westpowerelectric.com

Mobile: +86 18091765882(WhatsApp/Wechat/skype )

Website:https://www.xdtzelectrical.com

Add: Nanpo Village, Chencang Avenue Jintai District Baoji City, Shaanxi Province, China.