The insulation resistance test for vacuum circuit breakers is a key test for evaluating their insulation performance. The following is a detailed explanation:
1.Test Locations
Main circuit to ground: Insulation resistance between conductive parts (such as contacts and conductive rods) and the grounded housing.
Between phases (multi-pole circuit breakers): Insulation resistance between the conductive parts of each phase.
2. Test Instruments
Megohmmeter (Insulation Resistance Tester):
Voltage: Typically 1000V or 2500V DC (2500V is commonly used for 12kV circuit breakers).
Range: 0-10GΩ or higher (high resistance values require interference prevention).
Notes:
Before testing, disconnect the power supply and discharge the insulation (including parasitic capacitance).
Ambient humidity should be ≤ 80% to prevent condensation on the surface from affecting the results.
3. Test Procedure
1) Wiring:
Ground test: Connect the "L" terminal of the megohmmeter to the main circuit and the "E" terminal to the grounded housing.
Interruption test: In the open state, connect "L" to the moving contact and "E" to the static contact.
2) Measurement:
Read the stable value after 60 seconds at a constant speed (for manual megohmmeter) or in automatic mode (for absorption ratio test, record the 15s/60s ratio). 4) Recovery:
Discharge again after the test to prevent residual voltage hazards.
4. Acceptance Criteria
|
Test Location |
Minimum Requirements (Normal Temperature |
Remarks |
|
Main Circuit to Ground |
≥1000MΩ |
12kV and Above Equipment |
|
Inter-contact Gap |
≥5000MΩ |
Vacuum interrupter key indicators |
|
Between Phases (Open) |
≥1000MΩ |
1000MΩ Multi-Pole Circuit Breakers |
Abnormal Detection:
Value 50% below the standard: Moisture or contamination may be present.
Value drops sharply or approaches zero: Insulation breakdown or severe defects.
Example (12 kV vacuum circuit breaker)
Test voltage: 2500 V DC
Normal values:
Between interrupters: 10 GΩ (new interrupter chambers can reach over 100 GΩ)
To ground: 5 GΩ
Fault case: If the interrupter resistance is only 100 MΩ, the vacuum level may have deteriorated and the interrupter chamber may need to be replaced.
Insulation resistance testing is a fundamental maintenance measure for vacuum circuit breakers and should be combined with other tests (such as loop resistance and withstand voltage testing) to comprehensively assess the equipment's condition.

VTZ-12KF Fast Vacuum Circuit Breaker by Shaanxi West Power Tongzhong Electrical Co., Ltd. Is an indoor switchgear for rated voltage 12kV, AC 50/60Hz. It adopts modular operating mechanism and is suitable for various industrial and mining enterprises and power grid equipment. The trolley unit is used in conjunction with the KYN28A-12 switch cabinet. It can also be used as a fixed unit and equipped with corresponding mechanical interlocking for XGN2 and other fixed cabinets.
VTZ-12KF Fast Vacuum Circuit Breaker has many advantages:
1.Performance of circuit breaker:
E2-C2-M2
2.High adaptability:
This product is completely consistent with the cabinet switch size of the conventional KYN28-12 series, and does not require special cabinet design, which is suitable for a variety of occasions for transforming the power environment.
3.High conductivity:
Reasonable conductive circuit design, meeting the temperature rise level of 1.1 times the rated current;
4.Simple and reliable structure:
permanent magnet mechanism, three-phase independent design;
For more details ,pls cotact us :
Shaanxi West Power Tongzhong Electrical Co., Ltd.
Contact: Ms.Grace Liu (Director of Sales Department)
Tel: +86 917 3661109 Fax: +86 917 6739416
Email:xdtz04@westpowerelectric.com
Mobile: +86 18091765882(WhatsApp/Wechat/skype )
Website:https://www.xdtzelectrical.com
Add: Nanpo Village, Chencang Avenue Jintai District Baoji City, Shaanxi Province, China.