Pollution-related flashover and corrosion issues pronounced
In coastal, chemical, high-humidity, and high-altitude areas, switchgear has long faced the dual challenges of pollution flashover and corrosion. Pollution flashover refers to the flashover on insulator surfaces that occurs when dust, salt, or industrial pollutants accumulate on the insulating surface and form a conductive water film under wet conditions such as fog, dew, or light rain. Corrosion mainly comes from the erosion of metal parts, mechanism enclosures, and secondary wiring by salt spray, moist air, and chemical gases. In recent years, as renewable energy stations are deployed in coastal mudflats, northwestern deserts, and heavy industrial areas, these two problems have become more prominent.
Solutions to pollution flashover
Although the interrupter chamber of a vacuum circuit breaker is sealed and unaffected by external contamination and moisture, the external insulation bushings, supporting insulators, and operating mechanism are still exposed to the environment. To address pollution flashover, designs usually increase creepage distance and adopt silicone rubber composite insulation bushings or fully embedded poles. Silicone rubber is hydrophobic, making it difficult for water droplets on the surface to form a continuous conductive water film, thereby effectively suppressing pollution flashover. Fully embedded poles, on the other hand, cast the vacuum interrupter and conductive circuit integrally in insulating material, isolating them from external contamination.
Measures to address corrosion
To address corrosion, metal parts are mostly made of stainless steel or hot-dip galvanized, with anti-corrosion coatings applied to the surface; the protection class of the mechanism enclosure is raised to IP54 or above, and heating and dehumidifying devices are installed to prevent condensation. Secondary wiring uses sealed connectors to prevent moisture ingress. Salt spray testing is carried out in accordance with GB/T 2423.17 to verify product corrosion resistance. State Grid Corporation of China's Eighteen Major Anti-Accident Measures for Power Grids also explicitly require that switchgear in special environments should strengthen anti-pollution flashover, anti-corrosion, and anti-condensation measures.
The robustness of the design in these three aspects
At present, in scenarios such as coastal wind farms, plateau photovoltaic power stations, and chemical industrial parks, vacuum circuit breakers with the above adaptive designs have already been applied. Special environments are not assumptions in a laboratory but real operating conditions that equipment faces every day. Whether vacuum circuit breakers can pass this test depends on the solidity of the design in three aspects: insulation, corrosion protection, and sealing.

12KV/24KV/40.5KV Vacuum Circuit Breakers
Reliable Vacuum Circuit Breakers, Customized for Global Clients
Professional Technical&Sales Team | On-Time Delivery
Shaanxi West Power Tongzhong Electrical Co., Ltd.
Our address
No.1 East Gaoxin Avenue, High-tech Development Zone, Baoji City, Shaanxi Province, China
Phone Number
+86 18091767067(WhatsApp/Wechat)