Products

12kV Indoor Vacuum Circuit Breaker with Lateral Operating Mechanism for Medium Voltage Switchgear
HXGN-12 series ring main unit
5. Product Compliance with Standards: Complies with GB/T1984-2014 and G 2. Operating Mechanism: Modular operating mechanism
3. Installation Method: Ring main fixed cabinet
4. Compatible Cabinet: Compatible with B/T11022-2011 standards
6. Product Advantages: Features E2-C2-M2 performance, convenient maintenance, excellent insulation performance, and high adaptability

The 12kV Indoor Vacuum Circuit Breaker with Lateral Operating Mechanism for Medium Voltage Switchgear is designed for indoor switchgear with a rated voltage of 12kV and an AC frequency of 50/60Hz. It adopts a compact and practical structural design, providing reliable closing and opening performance for medium-voltage power distribution systems. The product is suitable for various indoor power distribution applications, offering stable operation and convenient installation and maintenance.
It incorporates our company's VTZ series modular operating mechanism and is developed as a derivative product of the series. The modular mechanism provides stable operation and convenient maintenance while allowing the circuit breaker to adapt to different switchgear configurations and installation requirements.
Featuring a lateral operating mechanism layout, the circuit breaker is well-suited for various industrial and mining enterprises, power grid equipment, and medium-voltage distribution applications. It is primarily designed for urban power supply ring main units, providing reliable switching, control, and protection for urban distribution networks and other applications requiring stable and dependable power supply.
Product Specifications
Specification Sheet
-
aiShenzhen Mandarin Oriental Hotel
|
No. |
Name |
Unit |
Data |
|
1 |
Rated Voltage |
kV |
12 |
|
2 |
Rated Frequency |
Hz |
50/60 |
|
3 |
Rated Current |
A |
630/1250/1600 |
|
4 |
Rated Power Frequency Withstand Voltage |
kV |
48(Across the contact gaps) / 42(To Ground) |
|
5 |
Rated Lightning Impulse Withstand Voltage |
kV |
75 |
|
6 |
Rated Short-Circuit Breaking Current |
kA |
25/31.5 |
|
7 |
Rated Short-Circuit Making Current (Peak) |
kA |
63/80 |
|
8 |
Rated Withstand Current (Peak) |
kA |
63/80 |
|
9 |
Rated Duration of Short-Circuit |
s |
4 |
|
10 |
Operating Cycles at Rated Short-Circuit Breaking Current |
Times |
E2 |
|
11 |
Mechanical Endurance |
Times |
10000 |
|
12 |
Standard Operating Sequence |
- |
O-0.3s-CO-180s-CO O-180s-CO-180s-CO |
|
13 |
Allowable Wear Thickness of Contact |
mm |
≤3 |
Mechanical characteristics
|
No. |
Name |
Unit |
Data |
|
1 |
Clearance between Moved and Fixed Contact |
mm |
9±1 |
|
2 |
Contact Overtravel |
mm |
3.5±0.5 |
|
3 |
Average Closing Speed |
m/s |
0.7±0.2 |
|
4 |
Average Opening Speed (Average Speed of First Opening at 6mm) |
m/s |
1.1±0.2 |
|
5 |
Rated Contact Pressure |
N |
2500±200N(25kA) 3100±200N(31.5kA) |
|
6 |
Closing Time |
ms |
30~70 |
|
7 |
Opening Time |
ms |
20~50 |
|
8 |
Contact Bouncing Duration at Closing Operation |
ms |
≤3 |
|
9 |
No-Simultaneity of Closing/Opening Operations of 3-Phase |
ms |
≤2 |
product advantages
The 12kV Vacuum Circuit Breaker with Lateral Operating Mechanism offers numerous advantages:
Breaker Performance
Meets E2-C2-M2 performance requirements, ensuring reliable electrical and mechanical endurance as well as stable switching performance under demanding operating conditions. This makes the circuit breaker suitable for applications requiring frequent operation and reliable fault interruption.
Convenient Maintenance
The modular mechanism design allows for easy replacement of closing and opening coils without disassembling other components. No testing or adjustment is required after replacement, enabling users to perform replacements independently and simplifying subsequent maintenance.
Excellent Insulation Performance
The main conductive circuit utilizes an APG high-strength epoxy resin composite insulated cylinder, providing excellent insulation performance that exceeds the requirements of relevant IEC standards. This robust insulation design also enhances the overall dielectric strength and operational reliability of the circuit breaker.
High Adaptability
The three phases of the circuit breaker are arranged from inside to outside, with a minimum cabinet depth of 900mm, making it suitable for various environments. The circuit breaker can be equipped with a mechanical interlock for seamless integration with the isolating switch and grounding switch of the cabinet, ensuring high safety.
Product Applications
The 12kV Vacuum Circuit Breaker with Lateral Operating Mechanism has many applications:
Urban community distribution systems
Mobile substation equipment
Industrial and mining enterprises
Product Outline Drawing

Note: The 12kV Vacuum Circuit Breaker with Lateral Operating Mechanism offers multiple configuration options:
- The primary conductive circuit main wiring can be positioned on either the left or right side.
- The main shaft of the 12kV circuit breaker with lateral operating mechanism can be extended to the left or right side, allowing the installation of corresponding parts for cabinet interlocking.
- Additionally, the opening mechanical operation lever can be extended to the left or right at the top, facilitating seamless connection to the cabinet to meet specific operational safety requirements for users.
Secondary Wiring Diagram

Our Retrofitting Solution
| Product Category | Specific Product | Applicable Scenarios |
| Vacuum Circuit Breakers | VS1-12, ZN63A-12, ZN12-12 | Replacement of original load switches or old circuit breakers |
| Operating Mechanism | Spring Mechanism (Electric/Manual) | Mechanism Damage, Manual to Electric Conversion |
| Insulator | Contact Box, Post Insulator, Bushing | Insulation Aging, Cracking |
| Vacuum Interruptor | 12kV General Type | Circuit Breaker Core Replacement |
| Intelligent Module | Current/Voltage Sensor, Communication Module | Intelligent Upgrade |
| Complete Cabinet | HXGN-12, XGN-12 | Severe Cabinet Damage, Complete Replacement |
Core Technical Points of HXGN-12 Retrofit
Circuit Breaker Selection
| Original Cabinet / Switchgear | Replacement VCB | Features |
| HXGN-12 (Load Switch Type) | VS1-12 | High versatility, compatible with ZN63A |
| HXGN-12 (Old-style Circuit Breaker) | ZN63A-12 | High cost-performance ratio, many retrofit cases |
| HXGN-12 (Frequency Operation Occasions) | ZN12-12 | Long mechanical life (30,000 cycles) |
Insulation component matching
Confirm the phase-to-phase distance and mounting hole spacing of the original cabinet.
Provide insulators, contact boxes, and bushings compatible with the original cabinet.
Custom sizes are available; direct replacement without modifying the cabinet.
Operating mechanism modification
Original manual mechanism → Converted to electric spring mechanism.
Mechanism damage → Replace with the same or compatible model.
Remote control module can be added for intelligent operation.
Contact Us

Contact: Melody Sun (Export Sales Manager)
Email: xdtz03@westpowerelectric.com
Mobile: +86 180 9176 5658 (WhatsApp)
Hot Tags: 12kV Indoor Vacuum Circuit Breaker with Lateral Operating Mechanism for Medium Voltage Switchgear, China 12kV Indoor Vacuum Circuit Breaker with Lateral Operating Mechanism for Medium Voltage Switchgear manufacturers, suppliers, factory, medium voltage switch equipment, VTZ 24 Vacuum Circuit Breaker, VTZ 12 Vacuum Circuit Breaker, ZN12 12 Vacuum Circuit Breaker, ZN85 40 5 Miniaturized Vacuum Circuit Breaker, VS1 12 Vacuum Circuit Breaker with Lateral Operating Mechanism
-
12kV 630A-5000A Indoor Medium Voltage Vacuum Circuit Brea...view more> -
VS1-12 Vacuum Circuit Breakerview more> -
ZN85-40.5 Vacuum Circuit Breakerview more> -
VS1-12 Indoor Vacuum Circuit Breaker with Lateral Operati...view more> -
ZN85-40.5 Miniaturized Indoor Vacuum Circuit Breakerview more> -
ZN12-12 Vacuum Circuit Breakerview more>







