Products

ZN42-27.5 Railway-Specific Vacuum Circuit Breaker
2. Operating Mechanism: Spring Operating Mechanism.
3. Installation Method: Floor handcart type.
4. Compatible Cabinet: Compatible with JYN-27.5 switchgear.
5. Product Compliance with Standards: JB6463-92, GB/T11022-2011.
6. Product Advantages: E2-C2-M2 performance, convenient maintenance, high conductivity performance, and supports intelligent customization.
ZN42-27.5 railway-specific vacuum circuit beaker is handcart structure and can be equipped with a special current transformer (LZZBJ-27.5) on the handcart. The design and manufacturing of this product comply with JB6463-92 "Technical Conditions for Circuit Breakers Used in Electrified Railways".
ZN42-27.5 railway-specific vacuum circuit beaker is suitable for electrified railway power supply systems with a rated voltage of 27.5kV and single-phase AC 50Hz, and it serves as a special switch for breaking/making load and breaking fault current. It can be installed individually within a grid interval or mounted in a JYN-27.5 switchgear. The operating mechanism of this product is a spring energy storage type. It can be electrically operated by AC or DC power, or manually operated.
Product Specifications
Specification Sheet
|
No. |
Name |
Unit |
Data |
|
1 |
Rated Voltage |
kV |
27.5 |
|
2 |
Rated Frequency |
Hz |
50 |
|
3 |
Rated Current |
A |
1250/1600/2000/2500 |
|
4 |
Rated Power Frequency Withstand Voltage |
kV |
95 |
|
5 |
Rated Lightning Impulse Withstand Voltage |
kV |
185 |
|
6 |
Rated Short-Circuit Breaking Current |
kA |
25/31.5 |
|
7 |
Rated Short-Circuit Making Current (Peak) |
kA |
63/80 |
|
8 |
Rated Withstand Current (Peak) |
kA |
63/80 |
|
9 |
Rated Duration of Short-Circuit |
s |
4 |
|
10 |
Operating Cycles at Rated Short-Circuit Breaking Current |
Cycles |
E2 |
|
11 |
Mechanical Endurance |
Times |
10000 |
|
12 |
Standard Operating Sequence |
- |
O-0.3s-CO-180s-CO |
|
13 |
Allowable Wear Thickness of Contact |
mm |
≤3 |
Mechanical characteristics
|
No. |
Name |
Unit |
Data |
|
1 |
Clearance between Moved and Fixed Contact |
mm |
16±1 |
|
2 |
Contact Overtravel |
mm |
4±1 |
|
3 |
Average Closing Speed |
m/s |
0.8±0.2 |
|
4 |
Average Opening Speed (Average Speed of First Opening at 12mm) |
m/s |
1.7±0.3 |
|
5 |
Rated Contact Pressure |
N |
3100±200N (25kA/31.5kA) |
|
6 |
Closing Time |
ms |
30~70 |
|
7 |
Opening Time |
ms |
20~50 |
|
8 |
Contact Bouncing Duration at Closing Operation |
ms |
≤3 |
|
9 |
No-Simultaneity of Closing/Opening Operations of 3-Phase |
ms |
≤2 |
ZN42-27.5 railway-specific vacuum circuit beaker has many advantages:
01
Performance of circuit breaker
E2-C2-M2
02
Convenient maintenance
the modular mechanism design allows for easy replacement of the closing and opening coils without the need for dismantling other components. This eliminates the need for testing or adjustment after replacement, ensuring users to replace them independently, making subsequent maintenance more convenient.
03
High conductivity performance
the main conductive circuit adopts a high-performance vacuum interrupter, providing a long electrical life.
04
Supports intelligent customization
it can be specially equipped with online monitoring devices to enhance system stability.
Product Applications
The product is specially designed for electrified railway power supply systems,
used for breaking/making load and breaking fault current.
Product Outline Drawing

Hot Tags: zn42-27.5 railway-specific vacuum circuit breaker, China zn42-27.5 railway-specific vacuum circuit breaker manufacturers, suppliers, factory, VTZ 12F Generator Output Specific Vacuum Circuit Breaker, ZN42 27 5 Railway Specific Vacuum Circuit Breaker, specific vacuum circuit breaker